Short answer: Specify one Somfy SDN 0-10V Interface V2 (1870857) per lighting zone, up to 30 SDN motors each. Give each interface its own group address on the Bank B DIP switches, leave bus power OFF on a device port, and program the lighting system to send fixed voltage steps.
A 0-10V shade tie-in fails in a loud way. The lighting contractor trims one room, and every shade on the floor drops during the owner's walkthrough. The fix is a DIP switch, but you pay for the ceiling access and the return trip. This guide puts those settings on the drawings before anyone opens a junction box.
Free spec package
Somfy SDN 0-10V Interface V2 lighting integration drawing set

- SMD-01 general notes and system limits with a source for every number
- SMD-02 input-to-position ladder, junction box detail and lead schedule
- SMD-03 riser, DIP switch and group address schedules, wiring schedule
- SMD-04 three-part guide spec, BOM and submittal checklist
Count one interface per lighting zone
The SDN 0-10V Interface V2 reads a standard 0-10V dimming signal and converts it to Somfy Digital Network commands. Each unit has one input and one address setting. That makes the takeoff simple: one shade zone, one interface.
Somfy rates each interface for up to 30 SDN tubular motors. A bigger zone needs a second interface and a second lighting output. Bank B offers 62 group addresses, so address count rarely limits a floor. The bus does: one segment carries 40 bus distribution devices and 200 end devices, and each interface counts as one end device.
Motor choice stays open. Somfy lists line-voltage RS485 motors such as the Sonesse 50 506S2 and Sonesse ULTRA 50 506A2, plus low-voltage motors such as the Sonesse 30 RS485. Glydea ULTRA RS485 drapery motors are on the same compatibility list.
Numbers to put in the spec
- Input power: 120V AC, 60 Hz, installed by an electrician
- Up to 30 SDN tubular motors per interface
- 62 group addresses, 010100 through 01013D
- Travel in 10% steps in SDN mode
- 200 ft maximum Cat5e stub from an SDN device port
- 20 SDN bus power units with the bus power switch ON
Set the group address before the lights go live
Somfy ships Bank B with all six switches down. That setting broadcasts to address FFFFFF, Motor All. On a one-zone bus, it works out of the box. On a shared bus, it moves everything.
Flip Bank B to a group address and the interface talks to that group alone. Switch 6 up gives 010100. Switch 5 up gives 010101. Switches 5 and 6 up give 010102. All six up is reserved, so skip it.
Our rule: read up as 1 and down as 0. Take the binary value, subtract 1, and you have the last byte of the address. Zone 4 reads 000100, or 4, so its address ends in 03.
The motors need the same group. Assign it in Set pro by Somfy through the USB to RS485 adaptor (9015260), using the Address ID column in Somfy's table. A job with a Somfy Connect UAI Plus can pull addresses from its Integration Report. SDN Keypad and SDN Motor Configuration Software read the Inverted ID column, so 010100 appears there as FFFEFE.
Choose the output mode on Bank A
Three switches decide how the interface behaves. All three ship up.
- Switch 1: up sends percent positions. Down sends intermediate positions IP1 through IP11.
- Switch 2: up runs SDN mode. Down runs animeo IP mode.
- Switch 3: up is standard direction. Down reverses it.
Percent mode needs no stored positions, which suits most offices. Intermediate positions let you store a custom drop at each window, so a tall sash and a short sash can land on the same sill line. That mode costs labor: every motor needs its positions programmed through Set pro or a UAI Plus.
animeo IP mode turns the interface into a 6-button non-ECO keypad in the animeo IP Visual Configuration software. Positions drop to five: 0%, 25%, 50%, 75% and 100%. Hold the push button 7 to 30 seconds to send the discovery signal.
Map the voltage the lighting system sends
Hand this table to the lighting programmer. In SDN mode, each level commands one position.
| Standard input | Encelium input | Shade position | Intermediate position |
|---|---|---|---|
| .750 V | .750 V | 0% | IP1 |
| 1 V | 1.088 V | 10% | IP2 |
| 2 V | 2.037 V | 20% | IP3 |
| 3 V | 2.973 V | 30% | IP4 |
| 4 V | 3.901 V | 40% | IP5 |
| 5 V | 4.897 V | 50% | IP6 |
| 6 V | 5.813 V | 60% | IP7 |
| 7 V | 6.73 V | 70% | IP8 |
| 8 V | 7.71 V | 80% | IP9 |
| 9 V | 8.66 V | 90% | IP10 |
| Prove on site | 9.58 V | 100% | IP11 |
Somfy's standard input table runs from .750 V to 9 V. Have the programmer send full-scale output during commissioning and confirm the shade reaches 100%. In animeo IP mode the bands widen: 0-3 V is UP, 3-4.7 V is 25%, 4.7-6.5 V is 50%, 6.5-8.2 V is 75%, and 8.2-10 V is DOWN.
Watch two traps. Somfy optimizes this control for discrete voltages over a sliding scale, which keeps motor position stable. A lighting fade feeds the interface a ramp, so give the shade output fixed steps with no fade time. Direction is the second trap. At 0% the shade sits up, and at 100% it sits down. If the lighting sequence needs the opposite, set Bank A switch 3 down and note it on the zone schedule.
Wireless lighting fits the same plan. Somfy and Casambi announced a partnership in April 2026 built on Casambi's wireless 0-10V interface, and Somfy lists a Casambi integration guide on the 1870857 product page. Pull that guide before you specify the Casambi side.
Match the bus power switch to the port
The bus power switch sits behind the access door. Left is OFF, right is ON, and the unit ships OFF. Plug into a device port on a Data Hub V2 or a PowerConnect surface-mount panel and the switch stays OFF. Somfy's wire details call for ON when the interface connects to a bus port, where it supplies 20 SDN bus power units.
Device ports hold one end device each, with stubs up to 200 ft on Cat5e or higher. The PowerConnect rack-mount panel gives you two device ports, same as the surface-mount panel. Terminate every bus cable to T-568B. Somfy says not to use RJ45 tees, splitters or passive hubs with SDN Connect.
Wire the box and the motors
The interface mounts to a junction box with a 1/2 in NPT lock nut, and its enclosure is plenum rated. That lets it sit in the ceiling next to the lighting device. Four 18 AWG leads land in the box:
- Black: line
- White: neutral
- Violet: 0-10V positive
- Pink: 0-10V negative
Motor cabling follows the distribution device. AC motors on a Data Hub V2 use the grey data cable with power (9018545), and two or more of them can power the hub. A single motor can plug straight into the interface with the black data-only cable (9018541). DC motors run from PowerConnect on SDN low-voltage cable, non-plenum 9020126 or plenum 9020127, up to 240 ft.
Commission in this order
- Set motor limits and power the motors.
- Assign each motor to its group.
- Land the leads with the 120V feed off. Verify 0-10V polarity.
- Set Bank A, Bank B and the bus power switch, then close the door.
- Energize. The main power LED shows solid green.
- Press and release the push button. The zone steps through up, stop, down, stop.
- Run every voltage level from the lighting system and watch the neighboring zone. It should hold still.
Our rule: write zone, DIP setting and address on the as-built. The next tech should never need a ladder to learn what a box does.
Take the spec package to your submittal
Somfy SDN 0-10V Interface V2 lighting integration drawing set
- SMD-01 general notes and system limits with a source for every number
- SMD-02 input-to-position ladder, junction box detail and lead schedule
- SMD-03 riser, DIP switch and group address schedules, wiring schedule
- SMD-04 three-part guide spec, BOM and submittal checklist
FAQ
How many shades can one SDN 0-10V Interface V2 control?
Somfy rates one interface for up to 30 SDN tubular motors. All of them follow the single address set on that interface, so one interface serves one shade zone.
Does the 0-10V Interface V2 need a separate 24V supply?
No. It runs on 120V AC, 60 Hz through its black and white leads. Its bus power switch can also supply 20 SDN bus power units when the interface connects to a bus port.
Should the bus power switch be on or off?
Leave it OFF, the factory position, when the interface plugs into an SDN device port on a Data Hub V2 or PowerConnect panel. Somfy's wire details call for ON when it connects to a bus port.
Can a lighting fade drive the shades?
Somfy optimizes this control for discrete voltages over a sliding scale, which keeps motor position stable. Program the lighting system to send fixed steps for the shade output and skip fade times.
Sources: Somfy SDN 0-10V Interface V2 Programming Guide v2.2 (Aug 2025); Somfy SDN 0-10V Interface V2 instructions 25000857 (4/2022) and wire details; Somfy Design Guide, SDN Connect v1.0 (Aug 2024); Somfy Data Hub V2 wire detail DH-WIRING-01; SDN PowerConnect Surface-Mount Panel spec sheet (2025); somfysystems.com product page 1870857; Residential Systems, Casambi and Somfy partnership (Apr 2026).