Short answer: Somfy shades earn their daylighting and glare points through the controls, so write the controls into the spec. On an SDN job, the SDN 0-10V Interface V2 (1870857) lets the lighting system set shade position in 10% steps. A DecoFlex SDN Keypad V2 gives occupants the override. animeo IP adds sun tracking with exterior sun sensors.
The daylighting credit lives in the sustainability consultant's binder. That binder needs a sequence of operations, a sensor layout and an override path from the shade spec. Miss one and the controls come back as a change order after the ceilings close. The fix costs less on paper than in a lift.
Free spec package
Somfy daylighting and glare control drawing set

- SMD-01 general notes and system limits with a source for every number
- SMD-02 keypad elevation with Somfy-published dimensions and the 0-10V J-box detail
- SMD-03 riser, 0-10V lead schedule, keypad RJ45 pinout and the IP1 to IP11 position map
- SMD-04 three-part guide spec language, BOM and a daylighting submittal checklist
The shade spec feeds the credit. The consultant claims it.
Somfy guide spec 12 25 09 carries a note to the specifier in Article 1.5: motorized shades can support LEED v4.1, WELL v2, Green Globes and IgCC credits during design and post construction. Article 1.5 C sends sustainability submittals to Division 01. The consultant picks the credit and writes the narrative. Your spec hands over the evidence.
Four items in 12 25 09 build that evidence:
- 1.4 B.3: a description of operations for the automation schedule.
- 1.4 B.4.d: sensor positioning diagrams.
- 2.2 B.8 and 2.3 D.7: a Type III EPD certified product environmental profile.
- 3.4 B: commissioning of the integrated automation controls and the BMS connection.
Somfy teaches this trade-off in an AIA course titled "Automated Window Coverings Influence on Well v2 and LEED v4.1 BD+C Equivalents, Alignments, & Tradeoffs" (1 LU with HSW). Send the design team to it before they write credit language around a control tier the job does not carry.
Pick the control tier before you write a word
12 25 09 names four ways to run Somfy shades on a daylit floor. Each one changes the riser, the submittals and who commissions the job.
Keypad-only SDN gives occupants groups and presets with no sensor input. Lighting-led control puts the 0-10V Interface V2 on the bus (Article 2.4 O). animeo IP solar management integrates solar tracking, timed events and digital keypads (Article 2.4 H), with up to 200 motors per Building Controller and Sub Controllers for more. BMS-led control uses the Somfy Connect BMS Interface V2: 4,500 data points over Modbus, BACnet MS/TP, BACnet IP or Metasys N2 (Article 2.4 M).
The guide spec note in 1.4 B.4 states that the system riser and the sensors work with Somfy digital network technology. Our rule: if the credit narrative mentions sensor-driven shades, the basis of design is SDN.
Lighting-led daylighting with the 0-10V Interface V2
Most daylit offices carry a lighting control system with photocells and schedules. The SDN 0-10V Interface V2 reads that system's 0-10V output and converts it into an SDN command for one motor or a group. The shades follow the same daylight logic as the lights. No BMS points, no second schedule.
The numbers to put in the spec:
- SDN mode moves motors in 10% increments, IP1 at 0% through IP11 at 100%. IP1 starts at 0.750 V.
- One interface drives up to 30 SDN tubular motors and supplies 20 SDN bus power units.
- DIP Bank A picks percent or intermediate position, SDN or animeo IP, and standard or reverse operation. DIP Bank B sets one of 62 group addresses. Motor All uses broadcast FFFFFF.
- Power is 120V AC line voltage. The plenum-rated enclosure mounts in a J-box beside the lighting device with a 1-1/2 in NPT lock nut.
The leads are color coded: black line, white neutral, purple 0-10V positive, pink 0-10V negative. Somfy says to verify input polarity before power goes on. The SDN side lands on one RJ45 over Cat5e or higher. Set the motor limits first. The programming guide requires a fully commissioned standalone SDN or animeo IP project, so Set pro and a USB to RS485 adaptor (9015260) belong on the commissioning list.
Our rule: meter the lighting controller's output floor and ceiling at commissioning and confirm both ends of the IP map move the shades to 0% and 100%.
Daylighting control limits to write into the spec
- 0-10V Interface V2: 10% steps, IP1 (0%) to IP11 (100%), IP1 at 0.750 V
- Up to 30 SDN motors and 20 bus power units per 0-10V Interface V2
- 62 group addresses on DIP Bank B; Motor All broadcast FFFFFF
- DecoFlex SDN Keypad V2: 24V DC from the bus, 140 mW max, 200 ft max to the SDN bus
- Group control keypads: 5 groups on 8 buttons, 3 groups on 6 buttons
- PowerConnect 1871026: 10 motor ports, 2 device ports, 240 ft max per motor run
Give occupants an override the sequence can live with
Automated glare control fails on day one if people cannot stop a shade. Article 2.4 L.4 of 12 25 09 lists a built-in override DecoFlex digital keypad. Specify it by name.
The DecoFlex SDN Keypad V2, 8-button (1871472) and the 6-button version (1871479) carry eight dry-contact inputs whatever the button count. Each button holds separate press, release and hold commands: limits, intermediate positions, percent, jog, lock and unlock. The keypad draws 140 mW max from the SDN bus at 24V DC, fits a single gang with a Decora plate and measures 1.44 x 1.5 x 4.06 in without the plate. Somfy recommends no more than 200 ft from keypad to the SDN bus.
For a facade split into zones, the 8-button Group Control keypad (1871496) runs up to five groups. The 6-button group version runs three. Group keypads support 255 command priority levels. Our rule: write the priority order into the description of operations.
On animeo IP, ECO-MODE lets the keypad push the zone back into automation. Our rule: write the return-to-automation behavior into the description of operations (1.4 B.3) so the consultant can show occupant control and automated glare control in the same narrative.
Sun tracking and sensors with animeo IP
Somfy's sun tracking sets shade position, and slat angle on Venetian blinds, from three inputs: sun position, building location and facade orientation. The building controller responds to the sun in real time.
Article 2.4 H covers the hardware. The solar management system draws 120 Vac at 1.25 A. Sensors mount on an Outside Sensor Box, and an extension box adds four more sun sensors. Article 3.3 H puts sun sensors on the exterior per Somfy's written instructions, and 1.4 B.4.d puts their positions on a diagram in the submittal.
The 0-10V Interface V2 also works in animeo IP mode. It then acts as a 6-button non-ECO keypad and maps the input to 0%, 25%, 50%, 75% and 100%. A lighting-led job can add animeo IP later without pulling the interface.
Motors, power and noise for occupied daylit rooms
Daylighting shades move all day in occupied rooms, so noise belongs in the spec. 12 25 09 writes motor classes at 38, 42, 47 and 55 dBA or less. The Sonesse ULTRA 50 RS485 24V DC (1134022) sits in the 38 dBA class at 4 Nm and 1.5 A. The Sonesse 30 RS485 24V DC (1241144) covers lighter shades on the same bus.
Power both from the SDN PowerConnect panel (1871026): 10 motor ports, 2 device ports and 240 ft max per motor run. Pull SDN motor power and data cable 9020126 for non-plenum spaces and the plenum version 9020127 above return-air ceilings. Somfy's guide spec 3.3 ties the installation to NFPA 70.
The daylighting submittal checklist
Hand the consultant this list with the shade submittal. Each line traces to 12 25 09:
- Description of operations: daylight response, schedules, override and return to automation (1.4 B.3).
- System riser and sensor positioning diagrams (1.4 B.4, 1.4 B.4.d).
- Type III EPD product environmental profile (2.2 B.8, 2.3 D.7).
- Commissioning record for the automation controls and any BMS connection (3.4 B).
Take the spec package to your submittal
Somfy daylighting and glare control drawing set
- SMD-01 general notes and system limits with a source for every number
- SMD-02 keypad elevation with Somfy-published dimensions and the 0-10V J-box detail
- SMD-03 riser, 0-10V lead schedule, keypad RJ45 pinout and the IP1 to IP11 position map
- SMD-04 three-part guide spec language, BOM and a daylighting submittal checklist
FAQ
Does a Somfy shade earn a LEED credit by itself?
No product earns a credit alone. The project team claims the credit. Somfy guide spec 12 25 09 notes that motorized shades can support LEED v4.1, WELL v2, Green Globes and IgCC credits, and it sends sustainability submittals to Division 01. Your spec supplies the sequence of operations, sensor diagrams, EPD and commissioning record.
Can a lighting control system drive Somfy shades without a BMS?
Yes. The SDN 0-10V Interface V2 (1870857) reads a standard 0-10V output and turns it into SDN commands for one motor or a group, in 10% steps from IP1 at 0% to IP11 at 100%. One interface drives up to 30 SDN motors.
How do occupants override automated Somfy shades?
A DecoFlex SDN Keypad V2 on the bus sends direct SDN commands, with separate press, release and hold actions per button. On animeo IP projects, ECO-MODE lets the keypad push the zone back into automation.
Does the 0-10V Interface V2 need its own low-voltage power supply?
No. It runs on 120V AC line power, mounts in a junction box in a plenum-rated enclosure and supplies 20 SDN bus power units. A qualified electrician makes the line connection.
Sources: Somfy guide specification 12 25 09 Motorized Window Shades (ARCAT, Articles 1.4, 1.5, 2.2 B.8, 2.3 D.7, 2.4 H, I, L, M, O, 3.3, 3.4); Somfy SDN 0-10V Interface V2 product page 1870857 (somfysystems.com); Somfy SDN 0-10V Interface V2 installation instructions and Programming Guide v2.2, Aug 2025; Somfy DecoFlex SDN Keypad and DecoFlex SDN Keypad Group Control spec sheets (Somfy OEM editions); Somfy DecoFlex SDN Keypad V2 product page 1871472 (somfysystems.com); Somfy sun tracking page (somfy.com projects, building controls); Somfy continuing education page (somfysystems.com, specifiers); Somfy Low-Voltage Databook and PowerConnect spec sheet (motor current, noise, port count, run length).
Ryan Towns writes the Somfy Integrator Guides for ShadeMotorsDirect, an authorized Somfy distributor. Questions on a spec or a retrofit: 859-414-6872 or colin@shademotorsdirect.com, 8:00 AM - 7:30 PM ET.