Short answer: SDN Data Hub V2 1870951 replaces the obsolete SDN Data Hub 1870262 on the same RJ45 runs. Land bus in, bus out and up to five device stubs, feed the hub motor power on grey power and data cables, then prove the swap with four LEDs and the SEQ button. Check two Somfy limits before you close the ceiling: 2,000 ft per bus power source and 40 bus distribution devices per segment.
One dead hub in a plenum ceiling stops every shade hanging off it. The swap takes minutes. The second trip comes from the parts you skip: a motor on the wrong cable, a stub past 24 ft with no coupler, or a segment that grew past its power budget while nobody counted. This guide covers the swap port by port, with the Somfy numbers that keep it to one visit.
Free spec package
SDN Data Hub V2 retrofit drawing set

- SMD-01 general notes and SDN Connect bus limits with sources
- SMD-02 Data Hub V2 dimensioned outline and mounting clip detail
- SMD-03 riser with bus power, hubs, Bus Booster and device stubs, plus 568-B pinout and LED schedules
- SMD-04 three-part guide spec, bill of materials and retrofit checklist
Is Data Hub V2 a drop-in replacement for Data Hub 1870262?
Yes, at the connector level. Somfy lists the SDN Data Hub 1870262 as obsolete and builds the SDN Connect range around SDN Data Hub V2 1870951, which Somfy calls the backbone of SDN Connect. Both hubs take RJ45 plugs, both protect connected devices from mis-wired power, ground or data, and both carry an IP 20 rating. Your existing Cat5e bus runs and device stubs stay in the ceiling.
The V2 brings five upgrades worth knowing before you quote the job:
- Five labeled device ports, with stubs up to 200 ft each.
- Motor power: two or more AC RS485 motors on its device ports run the hub and its devices.
- A SEQ button that runs a connected motor UP, STOP, DOWN from the hub.
- A mounting clip, a 1 W maximum draw and a UL 2043 plenum rating.
Our rule: photograph the old hub and tag every cable with its port name before you unplug anything. Bus in and bus out set the direction of the bus. A reversed pair shows up later as an End of Line LED in the wrong place.
Map the old ports onto the V2 ports
Data Hub V2 has one BUS IN jack, one BUS OUT jack and five DEVICE jacks. The cable from the bus power supply or the previous hub lands on BUS IN. The cable to the next hub or a Bus Booster lands on BUS OUT. Motors, keypads and an RTS receiver go on DEVICE ports. Somfy wires every jack to the 568-B standard: pin 1 Data +, pin 2 Data -, pins 4 and 5 Power +, pins 7 and 8 Ground, pins 3 and 6 reserved.
Each port takes a wiring stub of up to 200 ft. Somfy modular cables top out at 24 ft. Past 24 ft (7.3 m), Somfy calls for its Device Adaptor 9029460 or a generic RJ45 coupler with Cat5 or higher cable on the SDN pinout. Re-crimp any field plug you reuse. Somfy's troubleshooting steps start with strip length, bad crimps and a test with a second connector brand.
Use grey power and data cables so the motors power the hub
This is the change that saves bus power. With two or more AC RS485 motors on its device ports, such as the Sonesse ULTRA 50 506A2 RS485 1002566 or the Sonesse 506S2 RS485 1002286, Data Hub V2 and everything on it run on motor power. The yellow M LED confirms it. Somfy rates the hub to power three keypads such as the DecoFlex SDN Keypad V2 1871472, or one RTS Receiver for SDN V2 1871471.
Motor power reaches the hub through the grey power and data family: 2.5 ft 9018545, 8 ft 9018546, 12 ft 9018547 and 24 ft 9018548. Somfy's Data Hub V2 instructions name the 2.5 ft 4-conductor 26 AWG RJ9 to RJ45 cable 9018545 for connecting a motor to any data hub. The black family is data only and passes no motor power. Two motors on black cables leave the M LED dark, and the hub draws bus power you may not have budgeted.
Re-check the bus budget before you close the ceiling
Retrofits grow. A hub swap is the cheapest moment to count what the segment carries now. Somfy publishes the limits below for SDN Connect with Data Hub V2.
SDN Connect bus limits with Data Hub V2
- 2,000 ft of wiring per bus power source
- 2,000 ft max between two bus distribution devices
- 40 bus distribution devices per segment
- 200 ft max per device stub; 24 ft max on a modular cable
- Bus and Sensor Station Power Supply 1822440: up to 80 bus line devices, motors not counted
- Cat5e bend radius no tighter than 1 in
If the count runs past the budget, add power on the bus line. The SDN Bus Booster 9027694 fits a standard electrical box (a 4 x 4 x 1.5 in steel enclosure), wires straight to 120 V AC at 0.75 A and puts 24 V at 1 A on the bus. Somfy lets you place it anywhere on the bus without splitters or hubs, as an in-line segment extender or as standalone power for a segment. The Bus and Sensor Station Power Supply 1822440 stays the standard 24 V DC source at the head of a segment.
Our rule: write the device count and the cable footage on the hub label at handover. The next tech who adds a keypad starts from a number instead of a guess.
Mount Data Hub V2 on its clip
The V2 measures 4.66 x 2.63 x 1.33 in with its mounting clip and ships with the clip and two self-tapping screws for sheet metal or wood. Use a size 10 flat-head screw on any other surface. The hub is plenum rated to UL 2043 and is for indoor use only.
- No cables connected: slide the hub in from the side under the snaps until it clicks.
- Cables connected: angle the bottom of the hub into the two bottom snaps, then push until it snaps in.
- To remove: pull gently on the top snap.
- Dress Cat5e with no bend tighter than a 1 in radius.
Prove the swap with the LEDs, SEQ and Set pro
Four LEDs tell you whether the retrofit worked before you leave the lift:
- P, Bus Power (green): on means the hub has power.
- M, Powered by Motors (yellow): on means two motors feed the hub. Off with two motors plugged in: check for data-only cables, then press SEQ to look for a mis-wire.
- E, End of Line (yellow): on at the end of the bus. Lit in the wrong place: check that bus in and bus out are not reversed.
- A, Bus Activity (green): on when data is present. Lit on every hub: isolate the faulty device or segment by elimination. Dark: check the bus activity LED on the previous hub for a mis-wire between the two.
Press SEQ to run each connected motor UP, STOP, DOWN. Then plug the USB to RS485 Adaptor 9015260 into a device port and run a discovery in SDN Set pro by Somfy. Each SDN motor keeps its fixed 3-byte node ID, so the shade list and every integration driver should match the pre-swap schema. Save the schema to the job folder.
Take the spec package to your submittal
SDN Data Hub V2 retrofit drawing set
- SMD-01 general notes and SDN Connect bus limits with sources
- SMD-02 Data Hub V2 dimensioned outline and mounting clip detail
- SMD-03 riser with bus power, hubs, Bus Booster and device stubs, plus 568-B pinout and LED schedules
- SMD-04 three-part guide spec, bill of materials and retrofit checklist
FAQ
Is Somfy Data Hub V2 1870951 the replacement for Data Hub 1870262?
Somfy lists the SDN Data Hub 1870262 as obsolete and sells SDN Data Hub V2 1870951 as the SDN Connect bus distribution device. Both use RJ45 bus and device connections, so the V2 lands on the existing bus in, bus out and device runs.
How many device ports does Somfy Data Hub V2 have?
Five. Somfy says the V2 adds five device ports to an SDN bus line, with wiring stubs up to 200 ft per port. Bus in and bus out are separate RJ45 jacks.
Does Data Hub V2 need its own power supply?
No. With two or more AC RS485 motors on its device ports, the hub and its connected devices run on motor power. With fewer, they draw bus power from a bus power supply such as 1822440 or an SDN Bus Booster 9027694.
How far can I run the SDN bus with Data Hub V2?
Somfy's Data Hub V2 instructions set 2,000 ft of wiring per bus power source and 2,000 ft between two bus distribution devices, with up to 40 bus distribution devices on one segment.
Sources: Somfy product pages for SDN Data Hub 1870262, SDN Data Hub V2 1870951, SDN Bus Booster 9027694, Bus and Sensor Station Power Supply 1822440, RTS Receiver for SDN V2 1871471 and modular cable 9018545; somfypro.com e-cat 1870951; Somfy SDN Data Hub V2 spec sheet and SDN Bus Booster spec sheet (Somfy-built OEM copies); Somfy 1870951 SDN Data Hub V2 instructions, January 2024; Somfy SDN Integration Guide; SDN Set pro by Somfy User Guide V2.0.