An SDN bus runs out of room in two ways. An integrator adds the device that pushes a segment past 255 addresses, or a riser stretches past 4000 ft of bus wiring. The Somfy Data Panel, reference 1870260, answers both. It gives a system four isolated bus segments, each one rated for 255 devices and 4000 ft of bus wiring, and it supplies 100 power units. A DecoFlex SDN keypad sits on the front cover for local control of the motors on those segments.
Count the devices on each segment before you order
Somfy Digital Network addresses every motor, keypad, sensor and interface on the bus. Each device consumes an address and draws on the segment power budget. Somfy rates one isolated segment output on this panel at 255 devices and 4000 ft of bus wiring. Four of those outputs ship in one enclosure.
Specifiers reach for the Data Panel on two kinds of job. The first is a new commercial floor plate where the motor count already sits beyond what a single segment carries. The second is a retrofit that started small and grew, where an existing bus has run its length and the next wing of the building needs its own segment. Somfy publishes the panel as part of the SDN 2.0 certified product line, so the devices downstream of it carry the same bus behavior the design guides describe.
Jobs the Data Panel handles on an SDN bus
Isolation is the first job. Each of the four segment outputs stands apart from the other three, so a fault on one run does not pull the rest of the bus down with it. Somfy builds automatic segment termination into the panel and reports it through an end-of-line indication, which keeps signal integrity across the run without an installer setting a jumper at the far end.
Miswire protection is the second job. Somfy designed the panel to protect wired devices when power, ground or data wires land on the wrong terminal. Field crews pull hundreds of feet of cable in a riser, and a reversed pair at a termination point no longer takes a motor with it.
Patching is the third job. The panel carries common RJ45 ports with factory printed labels, so an installer lands each segment on a known port and reads the label back during commissioning. System status LEDs on the panel report bus power, SDN activity, SDN idle and end-of-line state. A technician standing at the enclosure can tell a dead segment from a quiet one.
Verified specifications
| Specification | Figure |
|---|---|
| Somfy reference | 1870260 |
| Somfy product name | Data Panel (SDN Data Panel) |
| Part type | SDN bus distribution panel |
| Isolated bus segments | 4 |
| Devices per segment | 255 |
| Bus wiring per segment | 4000 ft |
| Power units supplied | 100 |
| Power supply | AC 90-240 V, 50/60 Hz |
| Rated current | 3.35 A |
| Dimensions | 21.3 x 13.78 x 3.15 in |
| Weight | 18 lb |
| Protection index | IP 20 |
| Insulation class | Class II |
| Working temperature | 41 to 140 F |
| Storage temperature | From 32 F |
| Embedded technology | SDN |
| Color | Grey |
| Mounting | In-wall or on-wall enclosure, din rail inside |
| Approvals | CE, UL |
| Applications | Building management, interior blinds and shades |
| Warranty | 5 years |
Figures come from Somfy's published data for reference 1870260 on somfysystems.com and somfypro.com.
Parts that fit alongside the panel

Data distribution and motor power travel on separate paths in an SDN design. The Somfy Power Panel 24V for Somfy Digital Network feeds the low-voltage DC motors on the bus, while the Data Panel handles segment distribution and addressing. A building with both wired low-voltage and 120 V motors uses the Power Panel for the DC side of the plan.
Runs that reach past a segment limit get help from the Somfy SDN Bus Booster. Pair it with the panel when a riser or a long horizontal run sits at the edge of the published 4000 ft figure for a segment.
On the motor side, the Sonesse 50 510S2 RS485 SDN motor shows what the panel is built to carry. The motor speaks RS485 on the bus, takes an address, and reports position back to the head end. Interior shade projects with 120 V AC motors on an SDN bus run this family.
Somfy builds an SDN DecoFlex keypad into the panel itself. That gives the motors on the four segments a control point at the enclosure, which earns its keep during commissioning and during service calls years later. A technician drives a group from the panel face and confirms the segment answers before anyone walks the floor looking for a wall station. Larger floors want stations in the rooms, and the DecoFlex SDN Keypad V2 in 6-button white lands on the bus as another addressed device running the same scene and group logic from the occupied space. Count each one against the 255 device figure for its segment.
Install notes an integrator asks about
The enclosure mounts in the wall or on the wall, and Somfy separates the line voltage area from the low-voltage area inside. Electricians terminate the 90-240 V feed on one side while the low-voltage crew lands RJ45 segments on the other. Plan the rough-in around 21.3 by 13.78 in of face and 3.15 in of depth, and remember the 18 lb weight when you pick blocking for an on-wall mount.
Somfy ships a din rail inside the panel for an animeo IP Building Controller or Sub Controller. Jobs that put a head-end controller in the same enclosure as the bus distribution save a second box and a cable run between them. Confirm the controller model with the Somfy design guide for the project before you commit the space.
The front cover carries a keyed lock. Specify that where the panel lands in a corridor or a tenant space and the facilities team wants the bus out of reach. IP 20 and the 41 to 140 F working range put this panel inside conditioned space, so skip unconditioned attics, exterior walls and mechanical rooms that swing past those limits.
Growing an SDN system from this panel
Four segments change what a designer can promise on a floor. Add the panel to an existing bus and the next wing gets its own isolated run instead of a longer tail on a segment that already carries its share. Start a system with it and the first phase leaves room for the second without a rewire.
Order the Somfy SDN Data Panel (1870260) with the bus wiring plan in hand, since the segment count drives how many RJ45 home runs the electrician pulls back to the enclosure. Most projects add the Power Panel 24V at the same time, and a Bus Booster where a run stretches.
Frequently asked questions
How many devices does the Somfy Data Panel support?
Somfy rates each of the four isolated bus segment outputs at 255 devices and 4000 ft of bus wiring. Count every addressed device on a segment, including motors, keypads, sensors and interfaces, against that figure. The panel supplies 100 power units for the devices it serves.
What voltage does the Data Panel need?
Somfy publishes the power supply as AC 90-240 V at 50/60 Hz with a rated current of 3.35 A, so a standard 120 V line voltage circuit feeds it in North America. The enclosure separates the line voltage area from the low-voltage area, which keeps the electrical and low-voltage terminations apart.
Does the Data Panel include a keypad?
Yes. Somfy builds an SDN DecoFlex keypad into the panel for local control of the motors on its four bus segments. Rooms that need their own control point take a separate DecoFlex SDN keypad on the bus, and each one counts as an addressed device on its segment.
Can an animeo IP controller mount inside the Data Panel?
Somfy includes a din rail in the enclosure for mounting an animeo IP Building Controller or Sub Controller. That puts the head end and the bus distribution in one box. Check the controller's own dimensions and the project design guide before you plan the install around a shared enclosure.
Shade Motors Direct is an authorized source for genuine Somfy motorized window shade, blind, and drapery parts.